7SR181 Solkor Technical Manual
Chapter 4 - Page 62 of 80 © 2016 Siemens Protection Devices Limited
Counters
Static (Steady-State) Object Number: 20
Change Event Object Number: 22
Static Variation reported when variation 0 requested: 1 (32-Bit Counter with Flag)
or 2 (16-Bit Counter with Flag)
or 5 (32-Bit Counter w/o Flag)
or 6 (16-Bit Counter w/o Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter Event with Flag)
or 2 (16-Bit Counter Event with Flag)
or 5 (32-Bit Counter Event with Flag and Time)
or 6 (16-Bit Counter Event with Flag and Time)
Frozen Counters
Static (Steady-State) Object Number: 21
Change Event Object Number: 23
Static Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter with Flag)
or 2 (16-Bit Frozen Counter with Flag)
or 5 (32-Bit Frozen Counter with Flag and Time)
or 6 (16-Bit Frozen Counter with Flag and Time)
or 9 (32-Bit Frozen Counter w/o Flag)
or 10 (16-Bit Frozen Counter w/o Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter Event with Flag)
or 2 (16-Bit Frozen Counter Event with Flag)
or 5 (32-Bit Frozen Counter Event with Flag and Time)
or 6 (16-Bit Frozen Counter Event with Flag and Time)
Counter Frozen Counter
Point
Index
Description
Default
Change
Event
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Static
Object 20
Default
Variation
Event
Object 22
Deadband
Is Resettable
IsFreezable
Default
Change
Event
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Static
Object 21
Default
Variation
Event
Object 23
0 Waveform Records 0,3 5 1 1
✔
0,2 9 1
1 Fault Records 0,3 5 1 1
✔
0,2 9 1
2 Event Records 0,3 5 1 1
✔
0,2 9 1
3 Data Log Records 0,3 5 1 1
✔
0,2 9 1
5 StartCount 0,3 5 1 1
✔ ✔
0,2 9 1
6 Start Count Target 0,3 5 1 1
✔
0,2 9 1
7 Active Setting Group 0,3 5 1 1
✔
0,2 9 1
11 CB Total Trip Count 0,3 5 1 1
✔ ✔
0,2 9 1
12 CB Ph A Trip Count 0,3 5 1 1
✔ ✔
0,2 9 1
13 CB Ph B Trip Count 0,3 5 1 1
✔ ✔
0,2 9 1
14 CB Ph C Trip Count 0,3 5 1 1
✔ ✔
0,2 9 1
15 CB E/F Trip Count 0,3 5 1 1
✔ ✔
0,2 9 1
16 CB Delta Trip Count 0,3 5 1 1
✔ ✔
0,2 9 1
17 CB Count To AR Block 0,3 5 1 1
✔ ✔
0,2 9 1
18 CB Frequent Ops Count 0,3 5 1 1
✔ ✔
0,2 9 1
21 E1 Counter 0,3 5 1 1
✔
0,2 9 1
22 E2 Counter 0,3 5 1 1
✔
0,2 9 1
23 E3 Counter 0,3 5 1 1
✔
0,2 9 1
24 E4 Counter 0,3 5 1 1
✔
0,2 9 1
5.3.5 Analog Inputs
The following table lists Analog Inputs (Object 30). It is important to note that 16-bit and 32-bit variations of Analog
Inputs, Analog Output Control Blocks, and Analog Output Statuses are transmitted through DNP as signed numbers.