EasyManua.ls Logo

Siemens 7SR18 Solkor - Measurands

Siemens 7SR18 Solkor
417 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 - 7SR181 Solkor · Data Communications Definitions
© 2016 Siemens Protection Devices Limited Chapter 4 - Page 21 of 80
FUN INF Description ASDU COT
20 Ack, Nak
1 SE, GI
200 157 User SP Command 8
20 Ack, Nak
1 SE
200 158 User DP Command 1
20 Ack, Nak
1 SE
200 159 User DP Command 2
20 Ack, Nak
1 SE
200 160 User DP Command 3
20 Ack, Nak
1 SE
200 161 User DP Command 4
20 Ack, Nak
1 SE
200 162 User DP Command 5
20 Ack, Nak
1 SE
200 163 User DP Command 6
20 Ack, Nak
1 SE
200 164 User DP Command 7
20 Ack, Nak
1 SE
200 165 User DP Command 8
20 Ack, Nak
1 SE
200 200 CB 1 Trip & Reclose
20 Ack, Nak
1 SE
200 201 CB 1 Trip & Lockout
20 Ack, Nak
200 255 Blocked By Interlocking 1 SE, GI
255 0 General Interrogation (GI) Initiation 7 Init. GI
255 0 General Interrogation (GI) End 8 End of GI
255 0 Time Synchronisation 6
Time
Synch.
3.4.2 Measurands
The following Measurand EVT and INF numbers apply to this device.
FUN INF Description ASDU COT
183 148
Measurand I
L1,2,3,
V
L1,2,3,
P, Q, F, V
L1-2,L2-3,L3-1
---
I
L1
(2.4x) (Window 1%)
I
L2
(2.4x) (Window 1%)
I
L3
(2.4x) (Window 1%)
V
L1
(1.2x) (Window 1%)
V
L2
(1.2x) (Window 1%)
V
L3
(1.2x) (Window 1%)
P (2.4x) (Window 1%)
Q (2.4x) (Window 1%)
F (1.2x) (Window 0.1%)
V
L1-2
(1.2x) (Window 1%)
V
L2-3
(1.2x) (Window 1%)
V
L3-1
(1.2x) (Window 1%)
9
Cyclic -
Refresh
rate 5
seconds
or value
change
greater
than
Window x
%.

Table of Contents

Related product manuals