7SR18 Performance Specification
Unrestricted ©2018 Siemens Protection Devices Limited Page 25
of
2.6 50N Instantaneous Derived Earth Fault
2.6.1 Reference
Parameter Value
Is Setting 0.05, 0.06…2.5,2.55 …25.0,25.5…. 50 xIn
t
d
Delay setting
0.00, 0.01…20.00, 20.10… 100, 101… 1000, 1010…
10000, 10100… 14400 s
2.6.2 Operate and Reset Level
Attribute Value
I
op
Operate level
100 % Is, ± 5 % or ± 1 % In
Reset level
95 % I
op
Repeatability
± 1 %
Transient overreach
(X/R 100)
-5 %
Variation
-10 °C to +55 °C
5 %
f
nom
± 5 %
5 %
2.6.3 Operate and Reset Time
Attribute Value
t
basic
Element basic operate time
Switched from 0 to 2 xIs: 40 ms, ± 10 ms
Switched from 0 to 5 xIs: 30 ms, ± 10 ms
t
op
Operate time following delay
t
basic
+ t
d
, ± 1 % or ± 10 ms
Repeatability
± 1 % or ± 10 ms
Overshoot time < 40 ms
Disengaging time < 50 ms