7SR18 Commissioning & Maintenance Guide
Unrestricted Page 16 of 54 ©2018 Siemens Protection Devices Limited
2.6 PRIMARY INJECTION TESTS
Primary injection tests are to check the ratio and polarity of the current transformers as well as the secondary
wiring. Alternatively ‘On-Load’ tests may be conducted to speed to up test procedure.
Use the circuit shown in Figure 2.6-1 to check the current transformer ratio and the phase to earth connections.
Inject a current of sufficient magnitude for the relay ammeters to display. These values should be compared with
the ammeters connected in series with the relay.
Primary current
The secondary current is: Is = ––––––––––––––
C.T. ratio
Use the circuit shown in Figure 2.6-2 to check the current transformer ratio and the phase to phase connections.
Record the results: -
Phase
Injected
Primary
Current
Secondary Current
A
B
C
N
A-B Nil Nil
B-C Nil Nil
B-E Nil Nil
Figure 2.6-1 Primary Injection Phase to Earth