EasyManua.ls Logo

Siemens 7SR18 Solkor - Current Protection: Cold Load (51 C); Figure 3.6-1 Logic Diagram: Cold Load Settings (51 C)

Siemens 7SR18 Solkor
417 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR18 Description Of Operation
Unrestricted Page 44 of 78 ©2018 Siemens Protection Devices Limited
3.6 Current Protection: Cold Load (51c)
The setting of each shaped overcurrent element (51-n) can be inhibited and alternative ‘cold load’ settings (51c-n)
can be applied for a period following circuit switch in.
The Cold Load settings are applied after the circuit breaker has been open for longer than the Pick-Up Time
setting.
Following circuit breaker closure the ‘cold load’ overcurrent settings will revert to those defined in the Phase
Overcurrent menu (51-n) after either elapse of the Drop-Off Time setting or when the measured current falls
below the Reduced Current Level setting for a time in excess of Reduced Current Time setting.
During cold load settings conditions any directional settings applied in the Phase Overcurrent menu are still
applicable.
A CB ‘Don’t Believe It’ (DBI) alarm condition, see Section 4.3, is not acted on, causing the element to remain
operating in accordance with the relevant 51-n settings. Where the Reduced Current setting is set to OFF
reversion to 51-n settings will only occur at the end of the Drop-Off Time. If any element is picked up on expiry of
Drop-Off Time the relay will issue a trip (and lockout if a recloser is present).
If the circuit breaker is re-opened before expiry of the Drop-Off Time the drop-off timer is held but not reset.
Resetting the timer for each trip could result in damaging levels of current flowing for a prolonged period during a
rapid sequence of trips/closes.
Cold load trips use the same binary output(s) as the associated 51-n element.
Operation of the cold load element can be inhibited from:
Inhibit Cold Load A binary or virtual input.
Figure 3.6-1 Logic Diagram: Cold Load Settings (51c)

Table of Contents

Related product manuals