7SR18 Description Of Operation
Unrestricted ©2018 Siemens Protection Devices Limited Page 39 of 78
3.4.2 Instantaneous Derived Earth Fault Protection (50N)
Up to four instantaneous derived earth fault elements are provided in the relay (depending upon variant): -
50N-1, 50N-2, 50N-3 & 50N-4
Each instantaneous element has independent settings for pick-up current 50N-n Setting and a follower time
delay 50N-n Delay. The instantaneous elements have transient free operation.
Where directional elements are present the direction of operation can be set using 50N-n Dir. Control setting.
Directional logic is provided independently for each 50-n element.
Operation of the instantaneous earth fault elements can be inhibited from:
Inhibit 50N-n A binary or virtual input.
79 E/F Inst Trips: 50N-n When ‘delayed’ trips only are allowed in the auto-reclose sequence
(79 E/F Prot’n Trip n = Delayed).
50-n Inrush Action: Block Operation of the inrush current detector function.
50N-n VTSAction: Inhibit Operation of the VT Supervision function
Figure 3.4.2-1 Logic Diagram: Derived Instantaneous Earth Fault Element