7SR18 Solkor Settings Guide
Unrestricted
Page 10 of 44 © 2016 Siemens Protection Devices Limited
Description Range Default
Gn 50-1 Delay 0, 0.01 ... 14300, 14400 0s
Gn 50-1 VTS Action Off, Inhibit, Non-Dir Off
Gn 50-1 Inrush Action Off, Inhibit Off
8.1.6 50-2
Description Range Default
Gn 50-2 Element Disabled, Enabled Disabled
Gn 50-2 Dir. Control Non-Dir, Forward, Reverse Non-Dir
Gn 50-2 Setting 0.05, 0.06 ... 49.5, 50 1xIn
Gn 50-2 Delay 0, 0.01 ... 14300, 14400 0s
Gn 50-2 VTS Action Off, Inhibit, Non-Dir Off
Gn 50-2 Inrush Action Off, Inhibit Off
8.1.7 50-3
Description Range Default
Gn 50-3 Element Disabled, Enabled Disabled
Gn 50-3 Dir. Control Non-Dir, Forward, Reverse Non-Dir
Gn 50-3 Setting 0.05, 0.06 ... 49.5, 50 1xIn
Gn 50-3 Delay 0, 0.01 ... 14300, 14400 0s
Gn 50-3 VTS Action Off, Inhibit, Non-Dir Off
Gn 50-3 Inrush Action Off, Inhibit Off
8.1.8 50-4
Description Range Default
Gn 50-4 Element Disabled, Enabled Disabled
Gn 50-4 Dir. Control Non-Dir, Forward, Reverse Non-Dir
Gn 50-4 Setting 0.05, 0.06 ... 49.5, 50 1xIn
Gn 50-4 Delay 0, 0.01 ... 14300, 14400 0s
Gn 50-4 VTS Action Off, Inhibit, Non-Dir Off
Gn 50-4 Inrush Action Off, Inhibit Off
9 VOLTAGE CONT O/C
Description Range Default
Gn 51V Element (Ph-Ph) Disabled, Enabled Disabled
Gn 51V Setting 5, 5.5 ... 199.5, 200 30V
Gn 51V VTS Action Off, Inhibit Off
Gn 51-1 Multiplier 0.25, 0.3, 0.35, 0.4, 0.45, 0.5,
0.55, 0.6, 0.65, 0.7, 0.75, 0.8,
0.85, 0.9, 0.95, 1
0.5
Gn 51-2 Multiplier 0.25, 0.3, 0.35, 0.4, 0.45, 0.5,
0.55, 0.6, 0.65, 0.7, 0.75, 0.8,
0.85, 0.9, 0.95, 1
0.5
Gn 51-3 Multiplier 0.25, 0.3, 0.35, 0.4, 0.45, 0.5,
0.55, 0.6, 0.65, 0.7, 0.75, 0.8,
0.85, 0.9, 0.95, 1
0.5