7SR181 Solkor Technical Manual
Chapter 4 - Page 52 of 80 © 2016 Siemens Protection Devices Limited
Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
128 Trip Circuit Fail 3 0,2 2 2
129 CB Total Trip Count 0,2 2 2
130 CB Delta Trip Count 0,2 2 2
131 CB Count To AR Block 0,2 2 2
132 CB Frequent Ops Count 0,2 2 2
133 I^2t CB Wear 0,2 2 2
207 Close Circuit Fail 1 0,2 2 2
208 Close Circuit Fail 2 0,2 2 2
209 Close Circuit Fail 3 0,2 2 2
210 Close Circuit Fail 0,2 2 2
211 50BF Stage 1 0,2 2 2
212 50BF Stage 2 0,2 2 2
213 49-Alarm 0,2 2 2
214 49-Trip 0,2 2 2
217 37-1 0,2 2 2
218 37-2 0,2 2 2
219 CB Alarm 0,2 2 2
225 General Alarm 1 0,2 2 2
226 General Alarm 2 0,2 2 2
227 General Alarm 3 0,2 2 2
228 General Alarm 4 0,2 2 2
229 General Alarm 5 0,2 2 2
230 General Alarm 6 0,2 2 2
231 General Alarm 7 0,2 2 2
237 Quick Logic E1 0,2 2 2
238 Quick Logic E2 0,2 2 2
239 Quick Logic E3 0,2 2 2
240 Quick Logic E4 0,2 2 2
269 60 CTS-I 0,2 2 2
270 81HBL2 0,2 2 2
271 37G-1 0,2 2 2
272 37G-2 0,2 2 2
274 37-PhA 0,2 2 2
275 37-PhB 0,2 2 2
276 37-PhC 0,2 2 2
277 50 LC-1 0,2 2 2
278 50 LC-2 0,2 2 2
279 50G LC-1 0,2 2 2
280 50G LC-2 0,2 2 2
283 50BF-PhA 0,2 2 2
284 50BF-PhB 0,2 2 2
285 50BF-PhC 0,2 2 2