Chapter 4 - 7SR181 Solkor · Data Communications Definitions
© 2016 Siemens Protection Devices Limited Chapter 4 - Page 59 of 80
Binary Output Status Points
Static (Steady-State) Object Number: 10
Change Event Object Number: 11
Control Relay Output Blocks (CROB) Object Number: 12
Binary Output Command Event Object Number: 13
Static Variation reported when variation 0 requested: 1 (Binary Output w/o status)
or 2 (Binary Output with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time)
or 2 (Binary Output Event with Time)
Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time)
or 2 (Command Status with Time)
Point
Index
Description
Default
Change
Event
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Static
Object 10
Default
Variation
Event
Object 11
Default
Command
Event
Object 13
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Command
Event
Object 13
CROB
Supported
Operations
Default
CROB
Operations
59
Demand metering reset,
write only location.
0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
88 Remote mode 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
89 Service mode 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
90 Local mode 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
91 Local & Remote 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
98 Reset Start Count (Action) 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
Latch On
99 User SP Command 1. 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
100 User SP Command 2. 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
101 User SP Command 3. 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
102 User SP Command 4. 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
103 User SP Command 5. 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
104 User SP Command 6. 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
105 User SP Command 7. 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
106 User SP Command 8. 0 2 2 0 1
Pulse On
Latch On
Close
Pulse On
107 User DP Command 1. 0 2 2 0 1
Pulse On
Pulse Off
Latch On
Pulse On
Pulse Off