Chapter 4 - 7SR181 Solkor · Data Communications Definitions
© 2016 Siemens Protection Devices Limited Chapter 4 - Page 65 of 80
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Point
Index
Description
Default
Change Event
Assigned Class
(1, 2, 3 or none)
Default
Variation
Static
Object 30
Default
Variation
Event
Object 32
Default
Multiplier
Default
Deadband
102 Vn Primary 0,3 2 4 0.010 100.000
103 Vn Secondary 0,3 2 4 10.000 1.000
108 I Phase A Max 0,3 2 4 1.000 100.000
109 I Phase B Max 0,3 2 4 1.000 100.000
110 I Phase C Max 0,3 2 4 1.000 100.000
111 P 3P Max 0,3 2 4 0.000 1000000.000
112 Q 3P Max 0,3 2 4 0.000 1000000.000
135 CB Total Trip Count 0,3 1 3 1.000 1.000
136 CB Delta Trip Count 0,3 1 3 1.000 1.000
137 CB Count To AR Block 0,3 1 3 1.000 1.000
138 CB Frequent Ops Count 0,3 1 3 1.000 1.000
165 Ia Last Trip 0,3 1 3 1.000 Disabled
166 Ib Last Trip 0,3 1 3 1.000 Disabled
167 Ic Last Trip 0,3 1 3 1.000 Disabled
168 Va Last Trip 0,3 1 3 1.000 Disabled
169 Vb Last Trip 0,3 1 3 1.000 Disabled
170 Vc Last Trip 0,3 1 3 1.000 Disabled
171 In Last Trip 0,3 1 3 1.000 Disabled
172 Ig Last Trip 0,3 1 3 1.000 Disabled
174 V Phase A Max 0,3 2 4 0.010 100.000
175 V Phase B Max 0,3 2 4 0.010 100.000
176 V Phase C Max 0,3 2 4 0.010 100.000
177 V Phase AB Max 0,3 2 4 0.010 100.000
178 V Phase BC Max 0,3 2 4 0.010 100.000
179 V Phase CA Max 0,3 2 4 0.010 100.000
180 CB Ph A Trip Count 0,3 1 3 1.000 1.000
181 CB Ph B Trip Count 0,3 1 3 1.000 1.000
182 CB Ph C Trip Count 0,3 1 3 1.000 1.000
183 CB E/F Trip Count 0,3 1 3 1.000 1.000
184 CB Wear A 0,3 1 3 0.000 1000000.000
185 CB Wear B 0,3 1 3 0.000 1000000.000
186 CB Wear C 0,3 1 3 0.000 1000000.000
187 CB Wear A Remaining 0,3 1 3 1.000 1.000