7SR18 Commissioning & Maintenance Guide
Unrestricted Page 34 of 54 ©2018 Siemens Protection Devices Limited
3.6.1 DEFINITE TIME OVERCURRENT (50G)
If DTL setting is small, gradually increase current until element operates.
If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, check operation
Apply 2x setting current if possible and record operating time
Phase
Is
(Amps)
DTL
(sec)
P.U. Current
Amps
Operate Time
2 x Is
NOTES
I
4
Check correct indication, trip output, alarm contacts, waveform record.
3.6.2 INVERSE TIME OVERCURRENT (51G)
It will be advantageous to map the function being tested to temporarily drive the relevant Pickup output in the
Pickup Config sub-menu in the Output Config menu as this will allow the Pick-up led to operate for the function.
Gradually increase current until Pickup LED operates.
Apply 2x setting current and record operating time,
Apply 5x setting current and record operating time.
Compare to calculated values for operating times
P.U.
D.O.
&
TIMING
TESTS
Ph.
Char.
(NI EI VI LTI,
DTL)
Is
(A)
TM
Operate Current
Operate Time
P.U.
(Amps)
D.O.
(Amps)
Tol
2 x Is
(sec)
5 x Is
(sec)
Tol
I
4