7SR210 Settings Guide
Unrestricted Page 40 of 61 © 2018 Siemens Protection Devices Limited
3.7.2. Binary Input Config (Variants may differ)
Description Range Default
Inverted Inputs
Selects which inputs pickup when voltage is removed.
Combination of ( 1, 2, 3, 4, 5, 6, 7,
8, 9 )
---------
BI 1 Pick-up Delay
Delay on pickup of DC Binary Input 1
0, 0.005 ... 14300, 14400 0.02 s
BI 1 Drop-off Delay
Delay on dropoff of DC Binary Input 1
0, 0.005 ... 14300, 14400 0 s
-
BI 39 Pick-up Delay
Delay on pickup of DC Binary Input 9
0, 0.005 ... 14300, 14400 0.02 s
BI 39 Drop-off Delay
Delay on dropoff of DC Binary Input 9
0, 0.005 ... 14300, 14400 0 s
Enabled In Local
Selects which inputs are enabled when the relay is in
Operating Mode 'Local' or 'Local Or Remote'
Combination of ( 1, 2, 3, 4, 5, 6, 7,
8, 9 )
1, 2, 3, 4, 5, 6, 7,
8, 9
Enabled In Remote
Selects which inputs are enabled when the relay is in
Operating Mode 'Remote' or 'Local Or Remote'
Combination of ( 1, 2, 3, 4, 5, 6, 7,
8, 9 )
1, 2, 3, 4, 5, 6, 7,
8, 9