Siemens Argus 7SR22 - Operate and Reset Level; Operate and Reset Time; Instantaneous Measured Earth Fault; Reference

Siemens Argus 7SR22
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR21 & 7SR22 Performance Specification
Unrestricted © 2013 Siemens Protection Devices Limited Page 33 of 68
2.11 50G Instantaneous Measured Earth Fault
2.11.1 Reference
Parameter Value
Is Setting 0.005, 0.006… 25 xIn
i Applied Current (for operate time) From below Is to 2x Is & from below Is to 5x Is
t
d
Delay setting
0.00, 0.01…20.00, 20.50… 100, 101… 1000, 1010…
10000, 10100… 14400 s
2.11.2 Operate and Reset Level
Attribute Value
I
op
Operate level
100 % Is, ± 5 % or ± 1% In
Reset level
³ 95 % I
op
Repeatability
± 1 %
Transient overreach
(X/R £ 100)
£ -5 %
Variation
-10 °C to +55 °C
£ 5 %
f
nom
- 3 Hz to f
nom
+ 2 Hz
£ 5 %
2.11.3 Operate and Reset Time
Attribute Value
t
basic
Element basic operate time
Switched from 0 to 2x Is: 35 ms, ± 10 ms
Switched from 0 to 5x Is: 25 ms, ± 10 ms
t
op
Operate time following delay
t
basic
+ t
d
, ± 1 % or ± 10 ms
Repeatability
± 1 % or ± 10 ms
Overshoot time < 40 ms
Disengaging time < 50 ms