EasyManua.ls Logo

Siemens Argus 7SR22 - Power Protection; Power (32)

Siemens Argus 7SR22
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR210 & 7SR220 Applications Guide
Page 30 of 48 ©2018 Siemens Protection Devices Limited
2.17 Power Protection
2.17.1 Power (32)
Parallel Busbar Feeder
If power is fed to a busbar through two parallel infeeds, then in the event of any fault on one of these infeeds it
should be selectively interrupted. This ensures a continued supply to the busbar through the remaining the
remaining infeed. For this purpose directional devises are needed which detect a shortcircuit current or a power
flow from the busbar in the direction of the infeed. Reverse-power protection can be set far below the rated power.
Motor Protection
An under power element protects against a loss of load condition by measuring the real power flow. This feature
provides an alternative to under current measurement as load loss may result in only a small change in current.
The under power output is initiated by a voltage element operating after a definite time delay. The applied power
setting will typically be 10-20% below minimum load, the power and time delay settings must take into account:
Where rated power cannot be reached during starting (for example where the motor is started with no
connected load) it may be necessary to inhibit this function for a set time. This feature requires a 52a
circuit breaker auxiliary contact mapped to an opto input to get the information CB Closed/CB Open.
Directional power measurement may operate on occurrence of a system power supply fail or system
fault. Power flow into the motor will reverse since the motor will act as a generator due to the inertia of
the connected load.
General Calculation
Real, apparent or reactive power is set in the relay as a multiple of the relay (or secondary) nominal
power where: -
Nominal relay power (secondary) = relay nominal current x relay nominal voltage.
Example:
CT ratio = 400:1
VT ratio = 33000:110
Nominal secondary apparent power (S):
Nominal 3-phase VA (secondary) = 3 x V
L
x I
L
= 3 x 110 x 1
= 190.53 VA
= 1 xSn
When calculating the required operate value in primary quantities the CT and VT ratios must be
considered i.e. where the above corresponds to a nominal primary 3-phase apparent power (S) of:
Nominal 3-phase VA (primary) = 3 x V
L
x I
L
= 3 x 330000 x 400
= 22.863 MVA
= 1 xSn
The primary nominal VA calculated above may not match that of the protected primary plant and so
settings should be adjusted accordingly.

Table of Contents

Other manuals for Siemens Argus 7SR22

Related product manuals