7SR21 & 7SR22 Performance Specification
Unrestricted © 2013 Siemens Protection Devices Limited Page 63 of 68
3.7 81HBL5 Over Fluxing Detector
3.7.1 Reference
Parameter Value
I
Setting
(Ratio of 5th Harmonic current to
Fundamental component current)
0.10, 0.11... 0.5
3.7.2 Operate and Reset Level
Attribute Value
I
op
Operate level
100 % I, ± 4 % or ± 1% In
Reset level
100 % I
op
, ± 4 % or ± 1% In
Repeatability
± 1 %
Variation
-10 °C to +55 °C
£ 5 %
f
nom
- 3 Hz to f
nom
+ 2 Hz
£ 5 %
3.7.3 Operate and Reset Time
Attribute Value
t
basic
Element basic operate time
Will pick-up before operation of any protection element due
to overfluxing
Reset Time
Will operation until drop-off of any protection element due
to overfluxing