EasyManua.ls Logo

Siemens Argus 7SR22 - CT Supervision (60 CTS & 60 CTS-I); 60 Cts) - 7 Sr22; 60 Cts-I) - 7 Sr21 & 7 Sr22; Figure 5.4.1-1 Logic Diagram: CT Supervision Function (60 CTS-I) - 7 SR21 & 7 SR22

Siemens Argus 7SR22
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7SR210 & 7SR220 Description of Operation
Unrestricted Page 80 of 94 ©2018 Siemens Protection Devices Limited
5.4 CT Supervision (60CTS & 60CTS-I)
The relay has two methods of detecting a CT failure, depending on the relay variant.
5.4.1 (60CTS-I) – 7SR21 & 7SR22
The current from each of the Phase Current Transformers is monitored. If one or two of the three input currents
falls below the CT supervision current setting CTS-I for more than 60CTS-I Delay then a CT failure output
(60CTS-I Operated) is given. If all three input currents fall below the setting, CT failure is not raised.
Operation of the CT supervision elements can be inhibited from: -
Inhibit 60CTS-I A binary input, virtual input or remote data Comms.
60CTS-I Delay
IL1
IL2
IL3
60CTS I
<
Any 2 phases
but not all 3
&
Inhibit 60CTS
60CTS-I Element
Enabled
Disabled
60CTS-I Operated
Inhibit 60CTS
60CTS-I Pick-UP
60CTS-I Operated
&
Figure 5.4.1-1 Logic Diagram: CT Supervision Function (60CTS-I) – 7SR21 & 7SR22
5.4.2 (60CTS) – 7SR22
Normally the presence of negative phase sequence (NPS) current in a power system is accompanied by NPS
voltage. The presence of NPS current without NPS voltage is used to indicate a current transformer failure.
The element has a setting for NPS current level 60CTS Inps and a setting for NPS voltage level 60CTS Vnps. If
the negative sequence current exceeds its setting while the negative sequence voltage is below its setting for
more than 60CTS Delay then a CT failure output (60CTS Operated) is given.
Operation of the CT supervision elements can be inhibited from: -
Inhibit 60CTS A binary input, virtual input or remote data Comms.
&
60CTS Delay
VL1
VL2
VL3
NPS
Filter
V2
60CTS Vnps
<
IL1
IL2
IL3
NPS
Filter
I2
60CTS Inps
>
&
Inhibit 60CTS
60CTS Element
Enabled
Disabled
&
60CTS Operated
Inhibit 60CTS
60CTS Pick-Up
60CTS Operated
Figure 5.4.2-1 Logic Diagram: CT Supervision Function (60CTS) – 7SR22

Table of Contents

Other manuals for Siemens Argus 7SR22

Related product manuals