Unrestricted  ©2018 Siemens Protection Devices Limited Page 43 of 94
3.6  Current Protection: High Impedance Restricted Earth
Fault (64H)
One high impedance Restricted Earth Fault (REF) element is provided.
The relay utilises fundamental current measurement values for this function.
The  single  phase current input is derived  from the residual output  of line/neutral  CTs connected in parallel.  An
external stabilising resistor must be connected in series with this input to ensure that this element provides a high
impedance path.
64H Current Setting sets the pick-up current level. An output is given after elapse of the 64H Delay setting.
External  components  –  a series stabilising  resistor  and  a  non-linear resistor  –  are  used  with  this  function.  See
‘Applications Guide’ for advice in specifying suitable component values.
Operation of the high impedance element can be inhibited from: -
Inhibit 64H A binary or virtual input, function key or remote data Comms
Figure 3.6-1  Logic Diagram: High Impedance REF (64H)