7SR210 & 7SR220 Description of Operation
Unrestricted  ©2018 Siemens Protection Devices Limited Page 65 of 94
4.8  Manual Control
A  Manual  Close  Command  can  be  initiated  in  one  of  three  ways:  via  a Close  CB  binary  input,  via  the  data
communication Channel(s) or from the relay CONTROL MODE menu. It causes an instantaneous operation via
Manual Close CB binary output, over-riding any DAR sequence in progress.
Repeated Manual Closes  are avoided  by checking for Positive  edge  triggers. Even if the Manual  Close input is
constantly energised the relay will only attempt one close.
A Manual Close will initiate Line Check if Line  Check  Trip is enabled. If a fault  appears on  the  line during the
Close Pulse or during the Reclaim Time with Line Check enabled, the relay will initiate a Trip and Lockout. This
prevents  a  CB  being  repeatedly  closed  onto  a  faulted  line.  Where Line  Check  Trip  = DELAYED  then
instantaneous protection is inhibited until the reclaim time has elapsed.
Manual  Close  resets  Lockout,  if  the  conditions  that  caused  Lockout  have  reset, i.e.  there  is  no  trip  or Lockout
input present.
Manual Close cannot proceed if there is a Lockout input present.
With the Autoreclose function set to Disabled the Manual Close control is still active.
Close CB Delay
The Close CB Delay is applicable to manual CB close commands received through a Close CB binary input  or
via  the  Control  Menu.  Operation  of  the Manual  Close  CB  binary  output  is  delayed  by  the Close  CB  Delay
setting. The status of  this delay is displayed on the relay fascia as it decrements towards zero.  Only when the
delay reaches zero will the close command be issued and related functionality initiated.
Blocked Close Delay
The  close  command  may  be  delayed  by  a Block  Close  CB  signal  applied  to  a  binary  input.  This causes  the
feature to pause before it issues the CB close command and can be used, for example, to delay CB closure until
the CB energy has reached an acceptable level. If the Block signal has not been removed before the end of the
defined  time, Blocked  Close  Delay,  the  relay  will  go  to  the  lockout  state.  The  output Close  CB  Blocked
indicates this condition.
Open CB Delay
The Open CB Delay setting is applicable to CB trip commands received through an Open CB binary input or via
the Control Menu. Operation of the Open CB binary output is delayed by the Open CB Delay setting. The status
of this delay is displayed on the relay fascia as it decrements towards zero. Only when the delay reaches zero will
the trip command be issued and related functionality initiated.
It  should  be  noted  that  a  CB  trip  initiated  by  an Open  CB  command  is  fundamentally  different  from  a  CB  trip
initiated by a protection function. A CB trip caused by a CB Open command will not initiate functionality such as
circuit-breaker fail, fault data storage, I
2
t measurement and operation counter.
CB Controls Latched
CB controls for manually closing and tripping can be latched for extra security.
With Reset operation, the control resets when the binary input drops off. This can lead to multiple control restarts
due to bounce on the binary input signal.
With Latch operation, the close or trip sequence always continues to completion (or sequence failure) and bounce
on the binary input is ignored.
Reset  operation can be useful, however, as it allows a close or trip sequence to be aborted by dropping off the
binary input signal.