7SR210 & 7SR220 Description of Operation
Unrestricted  Page 84 of 94 ©2018 Siemens Protection Devices Limited
5.9  Load Blinder (21)
Load Blinders are used with directional overcurrent protection elements to block tripping during sustained heavy
load periods in distribution networks.
A Load Blinder element is provided in the 7SR22 relay with two operating modes, three-phase and single-phase.
5.9.1 Load Blinder (21) Three-Phase
Three-phase  mode  uses  positive  sequence  impedance  Z1.  Both  the  negative  sequence  overcurrent  threshold
(Blinder I2 > Block) and the under-voltage threshold (Blinder V< Block) are used to block the function.
21LB-3P Angle sets the angle for the load blinder region.
21LB-3P Impedance sets the impedance of the load blinder region.
21LB-3P VPPS  sets the level of positive phase sequence voltage.
21LB-3P IPPS  sets the level of negative phase sequence current.
Operation of the element can be inhibited from: -
Inhibit LB A binary input, virtual input, function key or remote data communications
The  design  of  Load  Blinder  3Ph  makes  consideration  that  protection  blocking  should  be  issued  only  during
definable allowable system power flow conditions i.e. an overcurrent blocking signal can only be issued when: -
a.  Positive  Sequence  Voltage Vpps is  not  significantly  changed,  when  the Vpps  is  above  the 21LB-3P
VPPS Setting.
AND
b.  Negative Sequence Current Inps is lower than 21LB-3P INPS Setting
AND
c.  Distributed  generators  feed  in  PPS  current  into  the  system.  In  case  of  high  load  in  system  due  to
distributed generation hence resulting in change of Zpps.
Zpps is calculated from Vpps and Ipps. The magnitude and angle of Zpps is compared with 21LB-3P
Impedance and 21LB-3P  Angle to  determine  if  the impedance  is in  operate  or  block and/or  FWD  or
REV zone.
Figure 5.9.1-1  Logic Diagram: Load Blinder Three-Phase