7SR220 Settings Guide
Unrestricted ©2018 Siemens Protection Devices Limited Page 45 of 107
Description Range Default
Gn 79 Cold Load Action
Selects whether whist Cold Load is active the relay will
perform only Delayed Trips or not.
Off, Delayed Off
3.11.2.1. P/F Shots
Description Range Default
Gn 79 P/F Prot'n Trip 1
Selects whether the first phase fault trip is Instantaneous
(Fast) or Delayed. When set to Delayed all P/F Inst Trips will
be Inhibited for this shot.
Inst, Delayed Inst
Gn 79 P/F Deadtime 1
Time period between the fault being cleared and the close
pulse being issued
0, 0.1 ... 14300, 14400 5 s
Gn 79 P/F Prot'n Trip 2
Selects whether the second phase fault trip is Instantaneous
(Fast) or Delayed. When set to Delayed all P/F Inst Trips will
be Inhibited for this shot.
Inst, Delayed Inst
Gn 79 P/F Deadtime 2
Time period between the fault being cleared and the close
pulse being issued
0, 0.1 ... 14300, 14400 5 s
Gn 79 P/F Prot'n Trip 3
Selects whether the third phase fault trip is Instantaneous
(Fast) or Delayed. When set to Delayed all P/F Inst Trips will
be Inhibited for this shot.
Inst, Delayed Delayed
Gn 79 P/F Deadtime 3
Time period between the fault being cleared and the close
pulse being issued
0, 0.1 ... 14300, 14400 5 s
Gn 79 P/F Prot'n Trip 4
Selects whether the fourth phase fault trip is Instantaneous
(Fast) or Delayed. When set to Delayed all P/F Inst Trips will
be Inhibited for this shot.
Inst, Delayed Delayed
Gn 79 P/F Deadtime 4
Time period between the fault being cleared and the close
pulse being issued
0, 0.1 ... 14300, 14400 5 s
Gn 79 P/F Prot'n Trip 5
Selects whether the fifth phase fault trip is Instantaneous
(Fast) or Delayed. When set to Delayed all P/F Inst Trips will
be Inhibited for this shot.
Inst, Delayed Delayed
Gn 79 P/F HS Trips To Lockout
Selects how many High Set trips are allowed before going to
Lockout
1, 2, 3, 4, 5 5
Gn 79 P/F Delayed Trips To Lockout
Selects how many Delayed trips are allowed before going to
Lockout
1, 2, 3, 4, 5 5
3.11.2.2. E/F Shots
Description Range Default
Gn 79 E/F Prot'n Trip 1
Selects whether the first earth fault trip is Instantaneous (Fast)
or Delayed. When set to Delayed all E/F Inst Trips will be
Inhibited for this shot.
Inst, Delayed Inst
Gn 79 E/F Deadtime 1
Time period between the fault being cleared and the close
pulse being issued
0, 0.1 ... 14300, 14400 5 s
Gn 79 E/F Prot'n Trip 2
Selects whether the second earth fault trip is Instantaneous
(Fast) or Delayed. When set to Delayed all E/F Inst Trips will
be Inhibited for this shot.
Inst, Delayed Inst