Chapter 4 - Data Communications Definitions
© 2017 Siemens Protection Devices Limited Chapter 4 - Page 25 of 96
FUN INF Description ASDU COT
91
7
LED PU 7
1
SE, GI
91
8
LED PU 8
1
SE, GI
91
9
LED PU 9
1
SE, GI
91 10 LED PU 10
1
SE, GI
91 11 LED PU 11
1
SE, GI
91 12 LED PU 12
1
SE, GI
91 13 LED PU 13
1
SE, GI
91 14 LED PU 14
1
SE, GI
91 15 LED PU 15
1
SE, GI
91 16 LED PU 16
1
SE, GI
160
2
Reset FCB
5
SE
160
3
Reset CU
5
SE
160
4
Start/Restart
5
SE
160
5
Power On
1
SE, GI
160 16 Auto-reclose active
1
SE, GI
20 Ack, Nak
160 19 LED Reset
1
SE
20 Ack, Nak
160 22 Settings changed
1
SE
160 23 Setting G1 selected
1
SE, GI
20 Ack, Nak
160 24 Setting G2 selected
1
SE, GI
20 Ack, Nak
160 25 Setting G3 selected
1
20
SE, GI
Ack, Nak
160 26 Setting G4 selected
1
20
SE, GI
Ack, Nak
160 27 Binary Input 1
1
SE, GI
160 28 Binary Input 2
1
SE, GI
160 29 Binary Input 3
1
SE, GI
160 30 Binary Input 4
1
SE, GI
160 36 Trip Circuit Fail
1
SE, GI
160 38 VT Fuse Failure
1
SE, GI
160 51 Earth Fault Forward/Line
2
SE, GI
160 52 Earth Fault Reverse/Busbar
2
SE, GI
160 64 Start/Pick-up L1
2
SE, GI
160 65 Start/Pick-up L2
2
SE, GI
160 66 Start/Pick-up L3
2
SE, GI
160 67 Start/Pick-up N
2
SE, GI
160 68 General Trip
2
SE
160 69 Trip L1
2
SE
160 70 Trip L2
2
SE
160 71 Trip L3
2
SE
160 73 Fault Impedance
1
SE
160 74 Fault Forward/Line
2
SE, GI
160 75 Fault Reverse/Busbar
2
SE, GI
160 84 General Start/Pick-up
2
SE, GI
160 85 Breaker Failure
2
SE