7SR220 Technical Manual
Chapter 4 - Page 60 of 96 © 2017 Siemens Protection Devices Limited
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function
Codes
(dec)
Qualifier Codes
(hex)
32
0
Analog Change Event
- Any Variation)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
32 1
32Bit-Analog Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32 2
16Bit-Analog Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
17, 28 (index)
(response)
130
(unsol. resp)
129
32 3
32Bit-Analog Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
(response)
130
17, 28 (index)
(unsol. resp)
32
4 (default -
see note 1)
16Bit-Analog Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
17, 28 (index)
(response)
130
(unsol. resp)
32 5
short floating point
Analog Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32 6
long floating point
Analog Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32 7
short floating point
Analog Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32 8
long floating point
Analog Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
33
0
Frozen Analog Event
- Any Variation
33 1
32-Bit Frozen Analog Event
(without Time)
33 2
16-Bit Frozen Analog Event
(without Time)
33 3
32-Bit Frozen Analog Event
(with Time)
33 4
16-Bit Frozen Analog Event
(with Time)
33 5
Short Floating Point
Frozen Analog Event
33 6
Long Floating Point
Frozen Analog Event
33 7
Extended Floating Point
Frozen Analog Event
34
34
0
1
Analog Input Deadband
(Variation 0 is used to
request default
variation)
16 bit Analog
Input
Deadband
1 (read)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
00, 01 (start-stop)
2 (write) 07, 08 (limited qty)
17, 27, 28 (index)
34
2 (default -
see note 1)
32 bit Analog
Input Deadband
1 (read)
2(write)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
34 3
Short Floating Point
Analog Input Deadband
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)

Table of Contents