7SR220 Technical Manual
Chapter 4 - Page 64 of 96 © 2017 Siemens Protection Devices Limited
Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class (1,
2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
85  81-6
0,2 2 2
86  51-3
0,2 2 2
87  50-3
0,2 2 2
88  51N-3 0,2 2 2
89  50N-3
0,2 2 2
90  51G-3
0,2 2 2
91  50G-3
0,2 2 2
92  51-4
0,2 2 2
93  50-4 0,2 2 2
94  51N-4
0,2 2 2
95  50N-4
0,2 2 2
96  51G-4
0,2 2 2
97  50G-4
0,2 2 2
98  Cold Load Active 0,2 2 2
99  E/F Out
0,2 2 2
100  P/F Inst Protection Inhibited 0,2 2 2
101  E/F Inst Protection Inhibited
0,2 2 2
102  SEF Inst Protection Inhibited
0,2 2 2
103  Ext Inst Protection Inhibited 0,2 2 2
117  51SEF-1
0,2 2 2
118  50SEF-1 0,2 2 2
119  51SEF-2
0,2 2 2
120  50SEF-2
0,2 2 2
121  51SEF-3 0,2 2 2
122  50SEF-3
0,2 2 2
123  51SEF-4 0,2 2 2
124  50SEF-4
0,2 2 2
125  SEF Out
0,2 2 2
126  Trip Circuit Fail 1 0,2 2 2
127  Trip Circuit Fail 2
0,2 2 2
128  Trip Circuit Fail 3
0,2 2 2
129  CB Total Trip Count
0,2 2 2
130  CB Delta Trip Count
0,2 2 2
131  CB Count To AR Block
0,2 2 2
132  CB Frequent Ops Count 0,2 2 2
133  I^2t CB Wear
0,2 2 2
207  Close Circuit Fail 1
0,2 2 2
208  Close Circuit Fail 2 0,2 2 2
209  Close Circuit Fail 3
0,2 2 2
210  Close Circuit Fail
0,2 2 2
211  50BF Stage 1 0,2 2 2
212  50BF Stage 2
0,2 2 2