EasyManua.ls Logo

Siemens Argus 7SR22 - Page 453

Siemens Argus 7SR22
644 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 - Data Communications Definitions
© 2017 Siemens Protection Devices Limited Chapter 4 - Page 73 of 96
Binary Output Status Points
Static (Steady-State) Object Number: 10
Change Event Object Number: 11
Control Relay Output Blocks (CROB) Object Number: 12
Binary Output Command Event Object Number: 13
Static Variation reported when variation 0 requested: 1 (Binary Output w/o status)
or 2 (Binary Output with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Output Event w/o Time)
or 2 (Binary Output Event with Time)
Command Event Variation reported when variation 0 requested: 1 (Command Status w/o Time)
or 2 (Command Status with Time)
Point
Description
Index
Default
Change
Event
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Static
Object 10
Default
Variation
Event
Object 11
Default
Command
Event
Object 13
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Command
Event
Object 13
CROB
Supported
Operations
Default
CROB
Operations
34 Settings Group 1 0 2 2 0 1
Pulse On
Latch On
Close
Latch On
35 Settings Group 2 0 2 2 0 1
Pulse On
Latch On Latch On
Close
Pulse On
36 Settings Group 3 0 2 2 0 1 Latch On Latch On
Close
37 Settings Group 4 0 2 2 0 1
Pulse On
Latch On Latch On
Close
Pulse On
38 Settings Group 5 0 2 2 0 1 Latch On Latch On
Close
39 Settings Group 6 0 2 2 0 1
Pulse On
Latch On
Close
Latch On
40 Settings Group 7 0 2 2 0 1
Pulse On
Latch On
Close
Latch On
41 Settings Group 8 0 2 2 0 1
Pulse On
Latch On
Close
Latch On
42 Auto-reclose on/off 0 2 2 0 1
Pulse On
Pulse Off
Latch On
Latch Off
Close
Trip
Pulse On
Pulse Off
Latch On
Latch Off
43 Hot Line Working on/off 0 2 2 0 1
Pulse On
Pulse Off Pulse On
Latch On
Latch Off
Pulse Off
Latch On
Close Latch Off
Trip
Pulse On
Pulse Off Pulse On
44 E/F Out on/off 0 2 2 0 1
Latch On
Latch Off
Pulse Off
Latch On
Close Latch Off
Trip
45 SEF Out on/off 0 2 2 0 1
Pulse On
Pulse Off
Latch On
Latch Off
Pulse On
Pulse Off
Latch On
Latch Off

Table of Contents