7SR220 Technical Manual
Chapter 4 - Page 84 of 96 © 2017 Siemens Protection Devices Limited
Setting Name Range/Options Default Setting Notes
Destination
Address
0 - 65534 0 As Required
Setting is only
visible when DNP3
Unsolicited Events
set to Enabled.
DNP3
Application
Timeout
5, 6 ... 299, 300 10s As Required
Setting is only visible
when any port
Protocol is set to
DNP3.