7SR210 & 7SR220 Applications Guide
Page 42 of 48 ©2018 Siemens Protection Devices Limited
5.5  Inrush Detector (81HBL2)
This element detects the presence of high levels of 2nd Harmonic current which is indicative of transformer Inrush
current  at  switch-on.  These  currents  may  be  above  the  operate  level  of  the  overcurrent  elements  for  a  short
duration  and  it  is important  that  the  relay  does  not  issue  an  incorrect  trip  command  for  this  transient  network
condition.
If a magnetic inrush condition is detected operation of the overcurrent elements can be blocked.
Calculation  of  the  magnetising  inrush  current  level  is  complex.  However  a  ratio  of  20%  2
nd
  Harmonic  to
Fundamental current will meet most applications without compromising the integrity of the Overcurrent protection.
There are 3 methods of detection and blocking during the passage of magnetising inrush current.
Phase Blocking only occurs in those phases where Inrush is detected.
Large, Single Phase Transformers – Auto-transformers.
Cross All 3-phases are blocked if Inrush is detected in any phase.
Traditional application for most Transformers but can give delayed operation for Switch-
on to Earth Fault conditions.
Sum Composite 2nd Harmonic content derived for all 3-phases and then compared to
Fundamental current for each individual phase.
Provides good compromise between Inrush stability and fast fault detection.
Table 5-5 Magnetic Inrush Bias
5.6  Broken Conductor / Load Imbalance (46BC)
This  feature is  used to  detect  an open  circuit  condition when  a  conductor  breaks or  a mal-operation occurs  in
phase segregated switchgear.
There  will  be  little  or  no  fault  current  and  so  overcurrent  elements  will  not  detect  the  condition.  However  the
condition can be detected because there will be a high content of NPS (unbalance) current present.
An NPS / PPS ratio > 50% will result from a Broken Conductor condition.
Operation is subject to a time delay to prevent operation for transitory effects.
5.7  Circuit-Breaker Maintenance
The Relay provides CB Total Trip Count, CB Delta Trip Count, CB Count to AR Block and CB Frequent Operation
Counters along with an I
2
t CB Wear Counter to estimate the amount of wear and tear experienced by a Circuit-
Breaker. Alarm can be provided once set levels have been exceeded.
Typically estimates obtained from previous circuit-breaker maintenance schedules or manufacturers data sheets
are used for setting these alarm levels. The relay instrumentation provides the current values of these counters.
5.8  Overfluxing Detector (81HBL5)
An increase in transformer or decrease in system frequency may result in the transformer becoming over-excited.
The  81HBL5 element can be  used  to  prevent  protection  operation  e.g.  prevent  differential protection operation
during acceptable over-excitation conditions.