Siemens Switzerland Ltd 
User manual RVS61.843 CE1U2355en_02 
HVAC Products  6 The settings in detail  23. November 2007 
Electric immersion heater  
Line no.  Operating line 
5060  El imm heater optg mode 
Substitute* ¦ Summer ¦ Always 
5061  El immersion heater release 
24h / day ¦ DHW release* ¦ Time program 4 
 
Substitute 
The electric immersion heater ensures DHW charging should the heat pump go to 
lockout, should it be off, or should DHW charging be aborted by the heat pump.  
If the electric immersion heater must ensure DHW charging because the heat pump 
was not able to complete the charging process, the controller saves the DHW 
temperature at which the electric immersion heater took over on operating line “Curr 
DHW charg temp HP”(7093). 
Also, at the changeover point, the switch-on temperature is readjusted. If the DHW 
temperature increases due to the electric immersion heater or some other heat source 
(e.g. solar), the switch-on point also increases according to the slave pointer principle. 
The switch-on point increases to a maximum of the current DHW setpoint minus the 
switching differential. If the DHW temperature falls below the switch-on point, the heat 
pump is put into operation. 
 
Summer 
When all heating circuits have switched to summer operation, the electric immersion 
heater ensures DHW charging from the next day. This means that the heat pump 
remains deactivated during summer operation. 
DHW heating via the heat pump is resumed only when at least one of the heating 
circuits has switched to heating mode.  
In heating mode, the electric immersion heater is operated as described above under 
“Substitute“. 
 
Always 
DHW charging is always provided by the electric immersion heater. 
 
The DHW operating mode button  
 also acts on the electric immersion heater. For 
the DHW to be heated, the DHW operating mode button must be pressed. 
 
24h/day 
The electric immersion heater is always released, independent of time programs. 
 
Example: 
 
 
DHW release 
The electric immersion heater is switched according to DHW release. 
 
El imm heater optg mode 
 
El imm heater release 
0 6121824
h
2358Z24