89/221 
Siemens Switzerland Ltd  User manual RVS61.843 CE1U2355en_02 
HVAC Products  6 The settings in detail  23. November 2007 
Cooling curve 
 
Line no.  Operating line 
908  Flow setp at OT 25°C 
909  Flow setp at OT 35°C 
The controller determines the required flow temperature at a certain composite outside 
temperature. The cooling curve is determined by defining 2 fixed points (flow 
temperature setpoint at 25 °C and 35 °C). 
This determines the flow temperature required for cooling at a composite outside 
temperature of 25 °C without giving consideration to summer compensation. 
This determines the flow temperature required for cooling at a composite outside 
temperature of 35 °C without giving consideration to summer compensation. 
 
 
 
TVKw  Flow temperature setpoint for cooling 
TAgem  Composite outside temperature 
 
The set cooling curve is based on a room temperature setpoint of 25 °C. If the room 
temperature setpoint is changed, the cooling curve automatically adapts to the new 
value. 
 
ECO 
 
Line no.  Operating line 
912  Cooling limit at OT 
913  Lock time at end of heating 
 
If the composite outside temperature lies above the cooling limit, cooling is released; 
cooling is locked when the outside temperature drops to at least 0.5 °C below the 
cooling limit. 
 
To avoid too rapid a change to cooling at the end of the heating phase, the cooling 
function is disabled for the period of time which can be set here. This locking period 
begins when there is no heating request from heating circuit 1. Heating requests from 
heating circuit 2 or heating circuit P are not taken into consideration. 
 
The locking time is aborted by switching the operating mode button off and on again. 
 
Summer compensation 
 
Line no.  Operating line 
Flow setp at OT 25°C 
Flow setp at OT 35 °C 
 
Cooling limit at OT 
Lock time at end  
of heating 
 
TVKw
35°C
TAgem
2355Z06
25°C
909