3-phase current 
For monitoring the 3-phase current, the 3 phases must be connected to inputs Ex5, Ex6 
and Ex7 in the correct order (L1, L2, and L3). The controller monitors the correct 
temporal order of the 3 phases. Any phase asymmetry, phase interruption or too low 
rated voltage of one or several phases is regarded as a 3-phase error.  
If a 3-phase error is continuously present during the period of time set under “Delay 3-
phase error” (2894), the compressor is switched off for the minimum off time. The 
controller delivers status message 
180: 3-phase current asymmetrical. 
If the 3-phase error occurs again within “Duration error repetition” (2889) for at least the 
delay time, the heat pump initiates lockout, if the preselected number of errors has 
been exceeded. The controller delivers error message 
355: 3-phase current 
asymmetrical
. The heat pump must be manually reset. 
 
Mixing group 
Line no.  Operating line 
6014  Function mixing group 1 
Heating circuit 1 
Cooling circuit 1 
Heating circuit/cooling circuit 1 
Prim contr/system pump 
DHW primary controller 
Instantaneous DHW heater 
 
Defines use of mixing group 1 and of its inputs and outputs. 
The settings are made on the respective menu (heating circuit 1, cooling circuit 1, etc.). 
The table below shows the logical assignment of the sensors / relays of the mixing 
group function to the physical terminals of the mixing group: 
 
Logical assignment of sensors and relays per 
mixing group function 
Physical terminal on 
the mixing group 
Designation of 
Heating circuit 1 
Cooling circuit 1 
Heating 
circuit/cooling 
 
DHW primary 
controller 
Instantaneous 
DHW heater 
B1 
p B1  B16 B1  B15 B35 B38 
Y1 
Y1  Y23 Y1  Y19 Y31 Y33 
Y2 
t 
Y2  Y24 Y2  Y20 Y32 Y34 
Q2 
s Q2 Q24 Q2 Q14 Q3 Q34 
 
 
Extension module 
Line no.  Operating line 
6020 
6021 
Function extension module 1, 2 
None 
Multifunctional 
Cooling circuit 1 
Heating circuit 2 
Solar DHW 
Primary contr/system pump 
DHW primary controller 
Instantaneous DHW heater 
 
 
Function mixing group 1