EasyManua.ls Logo

Siemens AVS75.390 - Wireless Outside Sensor AVS13.399

Siemens AVS75.390
221 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
210/221
Siemens Switzerland Ltd
User manual RVS61.843 CE1U2355en_02
HVAC Products 8 Technical data 23. November 2007
8.5 Wireless outside sensor AVS13.399
Batteries 2 pcs
Type of batteries
1.5 V alkaline size AAA (LR03)
Battery life Approx. 2 years
RF transmitter BSB-RF
Frequency band 868 MHz
Degree of protection of housing to
EN 60 529
IP20
Safety class to EN 60 730
Low-voltage-carrying parts meet the
requirements of safety class III, if correctly
installed
Degree of pollution to EN 60 730
Normal pollution
CE conformity to
EMC directive
- Immunity
- Emissions
Low-voltage directive
– Electrical safety
RF
89/336/EEC
- EN 61000-6-2
- EN 61000-6-3
73/23/EEC
- EN 60730-1, EN 50090-2-2
EN 300 220-1 (25-1000 MHz)
For devices without batteries:
Storage to EN 60721-3-1
Class 1K3, temperature -20…65 °C
Transport to EN 60721-3-2
Class 2K3, temperature -25…70 °C
Operation to EN 60721-3-3
Class 3K5, temperature 0...50 °C
(non-condensing)
For battery-powered devices:
Storage to EN 60721-3-1
class 1K3, temperature -20…30 °C
Transport to EN 60721-3-2
class 2K3, temperature -25…70 °C
Operation to EN 60721-3-3
class 3K5, temperature 0...50 °C
(non-condensing)
Outside sensor
QAC34/101
Measuring range -50…70 °C
Cable length Max. 5 m
Without packaging
Radio transmitter: 160 g
Outside sensor QAC34: 73 g
Cable: 70 g
Power supply
Interfaces
Degree of protection and
safety class
Standards, safety, EMC,
etc.
Climatic conditions
Outside temperature
acquisition
Weight