Remote control 
Line no.  Operating line 
HC1 HC2 HCP   
900  1200  1500  Optg mode changeover 
None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic 
 
In the case of external changeover via the Hx inputs, the operating mode to be used 
can be selected. 
 
Frost protection for the heating circuit 
Frost protection for the heating circuit is always active and cannot be deactivated. 
 
If the flow temperature falls below 5 °C, the controller switches on the heat source and 
activates the heating circuit pumps – independent of the heating system’s current 
operating mode. 
When the flow temperature returns to a level above 7 °C, the controller switches off the 
heat source and deactivates the heating circuit pumps after a waiting time of 5 minutes. 
For a more detailed description, refer to page 95. 
 
 
6.7  Cooling circuit 1 
 
 
RG1
B9
Y23/Y24
B16
Q24
C
 
To be able to operate the cooling circuit, an appropriate partial 
diagram “Heating / cooling“ must be used.  
The system starts to operate in cooling mode when the room 
temperature rises above the Comfort cooling setpoint (902). 
The cooling function must be activated (901 = Auto) and 
enabled in accordance with the time program (907). 
Cooling mode is aborted when heating circuit 1 calls for heat, 
or when there is a heat request from DHW or some other 
heating circuit (only with active cooling). 
In the case of passive cooling, DHW charging and heating 
with some other heating circuit during cooling mode are 
possible. 
When using a 2- or 4-pipe system with heat pump and process reversing valve, the 
controller acquires the current room temperature and compares it with the room 
temperature setpoint in order to calculate the required flow temperature setpoint. If the 
buffer storage tank temperature is sufficiently low, the cooling circuit draws the required 
cooling energy from that buffer. If the temperature is not low enough, or if there is no 
buffer storage tank, the heat pump is put into operation to be used as a refrigeration 
machine (process reversal Y22). 
2-pipe system 
Q2
HK
T
Y1/Y2
B1
Q24
KK
T
Y23/Y24
B16
 
 
The cooling and heating circuits draw their 
cooling / heating energy from the same 
common flow. 
 
When using a 4-pipe system, the controller acquires the current room temperature, 
compares it with the room temperature setpoint and then calculates the required flow 
Frost protection for the 
heating circuit in 
heating mode 
Frost protection for the 
heating circuit in cooling 
mode 
Cooling via common 
heating / cooling pipe 
Cooling via separate 
cooling pipe