Siemens Switzerland Ltd  User manual RVS61.843 CE1U2355en_02 
HVAC Products  6 The settings in detail  23. November 2007 
Release 
Line no.  Operating line 
1620 Release 
24h/day 
Time programs HCs 
Time program 4/DHW
 
 
 
24h/day 
The DHW temperature is maintained at the nominal DHW setpoint, independent of any 
time programs. 
 
Example: 
 
Time programs HCs 
The DHW setpoint changes between the nominal DHW setpoint and the reduced DHW 
setpoint according to the heating circuits’ time program. The first switch-on point of 
each phase is shifted forward in time by one hour. 
 
Example: 
 
 
Time program 4/DHW 
For DHW heating, time program 4 of the local controller is taken into consideration. The 
set switching times of that program are used to switch between the nominal DHW 
setpoint and the reduced DHW setpoint. This way, the DHW storage tank is charged 
independently of the heating circuits. 
 
Example: 
 
0 6121824
h
2371Z18
0 612 245
h
2377Z16
16 17
0 6121824
h
2373Z24