139/221 
Siemens Switzerland Ltd 
User manual RVS61.843 CE1U2355en_02 
HVAC Products  6 The settings in detail  23. November 2007 
Mixing valve control 
Line no.  Operating line 
5544  Actuator running time  
 
Setting the running time of the actuator used with the mixing valve. 
 
 
6.18 Configuration 
 
Procedure 
First, make use of the presetting choices and enter the plant diagram that comes 
closest to the plant in question. Then, modify manually the individual partial diagrams to 
match them to the actual requirements.  
After that, select the extra functions and make the fine-tuning via the operating lines of 
the individual parameters. 
 
Preselection of  
plant diagram 
Line no.  Operating line 
5700 Presetting 
 
The plant diagrams shown in chapter “Applications“ can be preselected by entering a 
diagram number. The plant diagram is the result of presetting plus the connected 
sensors. 
The sensors contained in the required plant diagram must be connected to ensure that 
automatic sensor identification will not detect some other plant diagram. 
 
Manual setting /  
adjustment of partial diagrams 
The plant diagrams consist of several partial diagrams. 
The required partial diagrams can be used to manually produce the required final plant 
diagram.  
But it is also possible to modify and adjust partial diagrams of a plant diagram 
generated via “Presetting” (5700). 
A catalog with partial diagrams, which is separately available, contains the partial 
diagrams implemented in the controller – classified according to groups. Also listed in 
the catalog are the required operating lines which must be set to produce the 
respective partial diagrams, plus the sensors required for the relevant partial diagram. 
 
You can use operating lines 6212 - 6217 (see page 162) to check if your adjustments 
led to the right partial diagram. The check no. shown there must accord with the 
relevant components group.  
 
ctuator running time 
Presetting