Number of times per week the temperature differential across the evaporator 
drops below the minimum  
Indicates how many times within a 7-day period the temperature differential across the 
evaporator may drop below the minimum. 
Number of times the temperature differential across the evaporator dropped below the 
minimum level within a 7-day period. If the value is above setting “Diff evap min/week“ 
(7082), symbol 
 appears on the display and a maintenance message on the info 
level: 
16: Diff evap min (priority 3) 
This parameter can be reset, provided the respective access right is granted. 
 
Interval for maintenance of DHW storage tank 
Setting of interval (in months) at which the DHW storage tank must be serviced. 
Period of time (in months) elapsed since last service visit. 
If the value is above setting “DHW storage tank interval“ (7090), symbol  
 appears on 
the display and a maintenance message on the info level: 
11: DHW storage tank interval (priority 6) 
This parameter can be reset, provided the respective access right is granted. 
 
Minimum DHW charging temperature 
Minimum temperature level to which the DHW storage tank must be charged by the 
heat pump with no abortion of charging. 
The controller saves the DHW temperature at which charging by the heat pump was 
last aborted since the heat pump has reached the limitation for high-pressure, hot-gas, 
or the maximum switch-off temperature.  
If the value is below setting “DHW charg temp HP min“ (7092), symbol  
 appears on 
the display and a maintenance message on the info level: 
12: DHW charg temp HP too low (priority 6) 
This parameter cannot be reset. 
When, next time the DHW storage tank is charged, the minimum DHW charging 
temperature is exceeded again, the maintenance function is cancelled. But if not 
reached again, the maintenance message is maintained. 
 
Other maintenance messages 
5:   Water pressure too low 
(priority 9) 
18: Water pressure 2 too low 
(priority 9) 
22: Water pressure 3 too low 
(priority 9) 
 
Economy mode 
7119 Economy function 
Locked ¦  released 
7120 Economy mode 
Off ¦ On 
 
Locked 
Economy mode is not possible. 
Diff evap min/week 
Cur diff evap min/week 
Reset 
DHW storage tank interval 
DHW stor tank since maint 
Reset 
DHW charg temp HP min 
Curr DHW charg temp HP 
No reset 
Economy function