75/221 
Siemens Switzerland Ltd  User manual RVS61.843 CE1U2355en_02 
HVAC Products  6 The settings in detail  23. November 2007 
6.4 Time programs 
 
For the heating circuits and DHW heating, a number of switching programs are 
available. They are activated in Automatic mode and control the change of the 
temperature levels (and the associated setpoints) via the selected switching times. 
 
The switching times can be set in a combined way, either commonly for several days, 
or separately for individual days. The preselection of groups of days like for instance 
Mo...Fr and Sa...Su that use the same switching times simplifies setting of the switching 
programs. 
Switching points 
Line no.  Operating line 
HC1 HC2 3/HCP 4/DHW 5   
500 520 540 560 600 Preselection 
Mo - Su 
Mo - Fr 
Sa - Su 
Mo - Su 
 
501 521 541 561 601 1. 1st phase on 
502 522 542 562 602 1. 1st phase off 
503  523  543  563  603 2. 2nd phase on 
504  524  544  564  604 2. 2nd phase off 
505 525 545 565 605 3. 3rd phase on 
506 526 546 566 606 3. 3rd phase off 
 
Standard program 
Line no.  Operating line 
516, 536, 556, 576, 
616 
Default values 
No 
Yes 
All time programs can be reset to their default settings. Each time program has its own 
operating line to make the reset. 
 
In that case, individual settings will be lost! 
 
6.5 Holidays 
 
 
Line no.  Operating line 
HC1 HC2 HC3P    
642 652 662   Start 
643 653 663   End 
648 658 668   Operating level 
Frost protection 
Reduced 
 
 
The holiday program is used to switch the heating circuits to a selectable operating 
level according to calendar dates. 
 
Important 
•  The holiday program can only be used in "Automatic" mode 
 
Entering the switching 
times