Structure and function
30
Building Technologies A6V10209291_f_en_--
Fire Safety & Security Products 05.02.2010
3.3.10 Test mode
For testing purposes the detector can be set to test mode. In test mode the
detector reacts faster and with a higher sensitivity level. The detector can be tested
with the detector exchanger and tester FDUD292 or the intelligent detector tester
FDUD293.
Electronic testing:
The detector can be tested with the detector exchanger and tester FDUD292 or the
intelligent detector tester FDUD293.
For details, see Documents 007227 and 009718.
Physical testing:
The optical function part on the neural fire detector can also be tested with the
test gas REF 8 or REF 8-S.
The heat sensors of the neural fire detector can be tested with a hot air fan.
The CO sensor can be tested with the test gas REF 8-C.
See also
Testing detectors [ 75]