Planning
49
Building Technologies A6V10209291_f_en_--
Fire Safety & Security Products 05.02.2010
4.2.2 Parameter sets: Sensor mode 0 'Technical CO alarm'
4.2.2.1 Description
(Parameter set numbers in brackets)
Robust EU1 (0):
Default parameter set with a static alarm threshold of 60 ppm CO. This parameter
set has a large compensation range and rapid compensation.
Balanced EU2 (1):
This parameter set corresponds to the dynamic CO alarm thresholds according to
EN 50291:2001. The parameter set has a small compensation range.
Static 40 (4):
This parameter set has a static alarm threshold of 40 ppm CO. The parameter set
has a small compensation range.
Static 50 (5):
This parameter set has a static alarm threshold of 50 ppm CO. The parameter set
has a small compensation range.
Static 60 (6):
This parameter set has a static alarm threshold of 60 ppm CO. The parameter set
has a small compensation range.
Balanced US1 (7):
This parameter set corresponds to the dynamic CO alarm thresholds according to
UL 2034. The parameter set has a small compensation range.
See also
Specification [ 51]