Maintenance / Repair
76
Building Technologies A6V10209291_f_en_--
Fire Safety & Security Products 05.02.2010
7.3.2 Testing the functionality of the 'Technical CO Alarm'
The following table shows the accessories with which the FDOOTC241 can be
tested in sensor mode 0.
Test gas Fire detector FDOOTC241 Detector
exchanger
and tester
Optical CO
Hot air
fan
Sensor mode 0 (Technical CO Alarm) X X
If detector FDOOTC241 is in test mode, the following must be noted:
Because the fire detection functionality is not automatically deactivated during test
mode for CO, the documentation provided for the control panel must be consulted
for details of how to proceed (for FS20 control panels as of MP2.1).
Deactivating the 'Technical CO Alarm' on the fire control panel does not
deactivate the fire detection functionality and the 'Technical Ambient Supervision
Alarm'.
If you are using CO test gases which haven't been approved, a fire alarm may be
activated during testing if additional setting of test mode is not undertaken on the
fire control panel.
If the detector is in alarm status, the internal alarm indicator flashes brightly every
second.
7.3.3 Testing the functionality of the 'Technical Ambient Supervision
Alarm'
You do not have to check the functionality of the 'Technical Ambient Supervision
Alarm' on a regular basis.
Testing the fire detection functionality and the Technical CO Alarm ensures that the
'Technical Ambient Supervision Alarm' also works.
See also
Testing the fire detection functionality [ 75]
Testing the functionality of the 'Technical CO Alarm' [ 76]
'Technical Ambient Supervision Alarm' performance check
[ 73]