Commissioning
73
Building Technologies A6V10209291_f_en_--
Fire Safety & Security Products 05.02.2010
6 Commissioning
The device is commissioned via the control panel. The exact procedure is
described in the control panel documentation.
Conduct a performance check once commissioning is complete.
See also
Performance check [ 74]
Testing the fire detection functionality [ 75]
Testing the functionality of the 'Technical CO Alarm' [ 76]
Testing the functionality of the 'Technical Ambient
Supervi
sion Alarm' [ 76]
6.1 'Technical Ambient Supervision Alarm' performance check
You cannot test whether the 'Technical Ambient Supervision Alarm' is functioning
correctly with test devices.
Checking can only take place indirectly:
You must know the current ambient temperature.
Enter the following parameters on the configuration tool:
A hysteresis range of 5 °C
A temperature threshold that is at least 5 °C below the current ambient
temperature.
Alarming when the threshold value is undershot
The detector sends a signal to the control panel
The 'Technical Ambient Supervision Alarm' is working correctly if the control
panel displays an alarm.