Planning
46
Building Technologies A6V10209291_f_en_--
Fire Safety & Security Products 05.02.2010
4.1.4.1 Application
Risk of injury to
persons
Concentration of
valuable items
Room geometry Deceptive
phenomena
Risk of fire Critical fire size No. Name
small …
large
low …
high
simple …
complex
few …
many
small …
large
small …
medium
2 Robust
1 Universal
3 Sensitive
4.1.5 Default settings
When delivered, the default parameter set (parameter set 0) is set in fire detector
FDOOTC241.
The following table shows the default parameter set in the various sensor modes.
Fire detector FDOOTC241 Default parameter set
Sensor mode 0 (neural fire detector) High Compensation
Sensor mode 1 (heat detector) A1R
Sensor mode 2 (smoke detector) Universal
Upon commissioning of the fire detection system, the optimum parameter set must
be selected based on the existing risk and the ambient conditions.
When the control panel is first started up, the fire detectors are automatically set to
their country-specific basic setting. Individual adaptation is performed using the
control panel's configuration tool.