Planning
42
Building Technologies A6V10209291_f_en_--
Fire Safety & Security Products 05.02.2010
High Compensation (7):
This parameter set reacts in the same way as the 'Robust (2)' parameter set,
however, the compensation range is twice as large. This parameter set is thus
especially suited for rooms in which a lot of dust and other deposits can be
expected during longer periods.
Robust (2):
The priority of the 'Robust (2)' parameter set is on robust response. The sensitivity
is the same as with the 'Suppression (5)' parameter set; however, deceptive
phenomena are not explicitly analyzed and suppressed. It is thus particularly suited
to application in rooms where deceptive phenomena such as cigarette smoke or
dust can be expected. The 'Robust (2)' parameter set is suitable for higher rooms
in comparison to the 'Suppression (5)' parameter set.
Balanced (4):
The 'Balanced (4)' parameter set displays a balanced response behavior in its
response to fires and robustness to deceptive phenomena. It reacts faster with
open fires. It reacts slower with vapor, cigarette smoke or smoldering fires.
Balanced CO (10):
This parameter set displays a balanced response behavior in its response to fires
and robustness to deceptive phenomena. It reacts faster with open fires. It reacts
slower with vapor and cigarette smoke. In the event of smoldering fires or fires in
cleaning rooms, the parameter set reacts quicker than the 'Balanced (4)' parameter
set as it takes the CO concentration into account.
Thanks to the fact that three criteria are evaluated (smoke, heat and CO
concentration), this gives particular robustness to deceptive phenomena when
compared with more sensitive parameter sets.
Fast Response (6):
This parameter set reacts in a fast and highly sensitive manner. It is thus especially
suited for rooms without deceptive phenomena, where the priority is on detecting
the fire as early as possible.
High Sensitive Fast (9):
This parameter set is suited for applications requiring very high sensitivity levels. It
reveals a significantly higher optical and thermal sensitivity than 'Fast Response
(6)'. This parameter set is also suited for applications that can otherwise only be
covered with special detectors.
Download 1 (14) / Download 2 (15):
Application-specific parameter sets that can be loaded on site (depending on the
control panel).