Fire department periphery module FCI2001-D1 [DE]
70
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
12.2.3 X5 fire department key depot
PIN Designation Description
8 Sabotage + Tamper monitoring (+)
7 Sabotage - Tamper monitoring (-)
6 Entriegel + Unlocking (+)
5 Entriegel - Unlocking (-)
4 Riegelkont + Latch contact (+)
3 Riegelkont - Latch contact (-)
2 Heizung + Heating (+)
1 Heizung - Heating (-)
Admissible cable cross-section: 0.2 ... 1.5 mm²
5
6
X5
Entriegel -
Entriegel +
7
8
Sabotage -
Sabotage +
1
2
Heizung -
Heizung +
3
4
Riegelkont -
Riegelkont +
2.2k
Ω
-
+
-
+
-
+
-
+
5
6
7
8
10
1
2
1*
2*
3*
5 W
1* Door contact 3* Key contact
2* Drill protection
When an alarm is pending, the key depot for the heating is disconnected from the
power supply for reasons of product safety. Only when the alarm is reset, is it
again connected to the power supply.