Fire department periphery module FCI2001-D1 [DE]
71
Building Technologies A6V10210410_a_en_--
Fire Safety & Security Products 18.05.2009
12.2.4 X6 intrusion detection system / local alarm / identification lamp
PIN Designation Description
8 Ke Leuchte + Identification lamp (+)
7 Ke Leuchte - Identification lamp (-)
6 Oertl Alarm + Local alarm (+)
5 Oertl Alarm - Local alarm (-)
4 - not used
3 FSD sabotage, closer (normally open)
2 FSD sabotage, common
1
FSD sabotage, opener (normally open)
Admissible cable cross-section: 0.2 ... 1.5 mm²
5
6
X6
Oertl Alarm -
Oertl Alarm +
7
8
Ke Leuchte -
Ke Leuchte +
2
3
4
2
1
-
+
-
+
40 ... 2kΩΩ
1*
2*
2*
3*
300mA / max. 7.5W
560
2W
3*
1* Horn or beacon 3* If necessary
2* FSD sabotage, connection for
"Transmission intrusion detection
system" (can be connected as NO or
NC)