6
Fault rectification
A
larms and faults
50
Siemens AG CM2G5111en
2014-05-16
Number Cause Solution
3. Recommission the drive.
F01033 Unit switchover: Reference parameter
value invalid
Set the value of the reference parameter not equal to 0.0 (p0304, p0305,
p0310, p0596, p2000, p2001, p2002, p2003, r2004).
F01034 Unit switchover: Calculation of the
parameter values after reference value
change unsuccessful
Select the value of the reference parameter so that the parameters involved can
be calculated in the representation (p0304, p0305, p0310, p0596, p2000,
p2001, p2002, p2003, r2004).
F01040 Parameters must be saved
Save the parameters (p0971).
Switch the CU off and on again.
F01044 Fault loading the data from the
memory card
Replace the memory card of the CU.
F01105 Insufficient memory
Reduce the number of data records.
F01122 Frequency at the probe input too high
Reduce the frequency of the pulses at the measuring input.
F01205 Time slice overflow
Contact Technical Support.
F01250 CU hardware fault
Replace the CU.
F01512 No scaling An attempt has been made to establish a conversion factor for scaling which is not
present.
Apply scaling or check the transfer value.
F01662 CU hardware fault
Switch the CU off and on again.
Update the firmware.
Contact Technical Support.
A01910
F01910
Setpoint timeout: p2040 ≠ 0 ms and
one of the following causes:
The bus connection is interrupted
The MODBUS master is switched
off
Communications error (CRC,
parity bit, logical error)
Establish the bus connection and switch on the communication partners.
Possibly adapt p2040.
Set the PROFIBUS master to RUN.
F03505 Analog input, wire break
Check the connection with the signal source for interruptions.
Check the level of the signal which is fed in.
The input current measured by the analog input can be read in r0752.
F06310 Supply voltage (p0210) incorrectly
parameterized
Check the supply voltage and change the parameter (p0210), if necessary.
Check the line voltage.
F07011 Motor overtemperature
Reduce the motor load.
Check the ambient temperature and the motor ventilation.
Check the wiring and the connection of the sensor.
F07016 Motor temperature sensor fault
Check that the sensor is correctly connected.
Check the parameter assignment (p0601).
Switch off the temperature sensor error (p0607 = 0).
F07086
F07088
Unit switchover: Parameter limit
violation
Check the adapted parameter value and correct it, if necessary.
F07320 Automatic restart aborted
Increase the number of restart attempts (p1211). The actual number of start
attempts is shown in r1214.
Increase the waiting time in p1212 or the monitoring time in p1213.
Apply the ON command (p0840).
Increase the monitoring time of the power unit or disable the monitoring time
(p0857).
Reduce the waiting time for resetting the fault counter p1213[1] so that fewer
faults are registered in the time interval.
F07330 Search current measured too low
Increase the search current (p1202).