EasyManua.ls Logo

Siemens MICROMASTER 430 - Page 100

Siemens MICROMASTER 430
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Information for the CANopen master Issue 01/05
CANopen Option Module Operating Instructions
100 6SE6400-5BC00-0BP0
Set the number of mapped objects to 2
Write 2 into object 0x1605 sub 0
T0 00:01:54,9624: 0x603 8-Data: 2f 05 16 00 02 00 00 00
R0 00:01:56,6833: 0x583 8-Data: 60 05 16 00 00 00 00 00
5.8.1.3 Execute the mapping for TPDO 5
Set the number of mapped objects to 0
Write 0 into object 0x1A05 sub 0
T0 00:01:56,7626: 0x603 8-Data: 2f 05 1a 00 00 00 00 00
R0 00:01:56,7748: 0x583 8-Data: 60 05 1a 00 00 00 00 00
The status word is the first mapped object:
Write 0x60410010 into object 0x1A05 sub 1
T0 00:01:56,8695: 0x603 8-Data: 23 05 1a 01 10 00 41 60
R0 00:01:56,8819: 0x583 8-Data: 60 05 1a 01 00 00 00 00
Modes of operation display is the second mapped object:
Write 0x60610008 into object 0x1605 sub 2
T0 00:01:56,9977: 0x603 8-Data: 23 05 1a 02 08 00 61 60
R0 00:01:57,0108: 0x583 8-Data: 60 05 1a 02 00 00 00 00
Set the number of mapped objects to 2
Write 2 into object 0x1A05 sub 0
T0 00:01:57,1004: 0x603 8-Data: 2f 05 1a 00 02 00 00 00
R0 00:01:58,7806: 0x583 8-Data: 60 05 1a 00 00 00 00 00
Set the nodes into the operational mode:
T0 00:01:58,8546: 0x000 2-Data: 01 03
Receive the three PDOs:
R0 00:01:58,8655: 0x183 2-Data: 31 fe
R0 00:01:58,8741: 0x283 4-Data: 31 fe 00 00
R0 00:01:58,8816: 0x383 3-Data: 31 fe 04

Table of Contents

Other manuals for Siemens MICROMASTER 430

Related product manuals