Issue 01/05  Information for the CANopen master 
CANopen Option Module    Operating Instructions 
6SE6400-5BC00-0BP0 
77 
In order to set the mapping for PDO 5 or PDO 6 via the CANopen master, the 
usual sequence must be maintained (also refer to DS 301): 
1/ Set the number of mapping entries in the subindex 0 to 0  
2/ Write new mapping entries - one after the other - into sub-indices 1 to 4  
3/ Set the number of mapping entries in subindex 0 to the number of the now newly 
mapped objects (2 for 2 mapping entries, 4 for 4 mapping entries...) 
NOTE 
The internal MICROMASTER parameters only use a single bit in order to specify a 
mapping parameter. This is the reason that in CANopen, a specific sequence must 
be maintained when writing the mapping values. The connection between drive 
parameters and mapping entry is specified in the following table: 
Direction Mapping  Saved 
mapping value
Mapping sequence  Bit number in 
P2041.02 or 
P2041.03 
R_PDO  Control word  60400010  1 (lowest mapping index)  Bit 0 
R_PDO  Setpoint (reference) speed  60420010H or 
60520010H 
2 Bit 1 
R_PDO  Free object 2802 subindex 3  28020310H  3  Bit 2 
R_PDO  Free object 2802 subindex 3  28020410H  4  Bit 3 
R_PDO  Setpoint (reference) torque  60710010H 5  Bit 4 
R_PDO  Free object 2802 subindex 3  28020610H  6  Bit 5 
R_PDO  Modes of operation   60600008H  7 (highest mapping index)  Bit 6 
R_PDO  Select RPM or per unit  -  -  Bit 7 
T_PDO  Status word  60410010H  1 (lowest mapping index)  Bit 8 
T_PDO  Speed control quantity  60430010H or 
60530010H 
2 Bit 9 
T_PDO  Free object 2803 index 3  28030310H  3  Bit 10 
T_PDO  Free object 2803 index 4  28030410H  4  Bit 11 
T_PDO Actual torque  60770010H 5  Bit 12 
T_PDO Actual speed  60440010H or 
60540010H 
6 Bit 13 
T_PDO  Displays the operating mode   60610008H  7 (highest mapping index)  Bit 14 
T_PDO  Select RPM or per unit  -  -  Bit 15 
 
 Objects can only be mapped in MICROMASTER 440