Parameter accessing error (r2054.04), error numbers < 240 correspond to PKW
error numbers:
Table 7-5
1R &DXVH 5HPHG\HJLQ3UR7RRO
No. 0 .. 199: Parameter access has been converted to a PKW request. Error detected in converter.
Additional info in r2054.05, r2054.06: Parameter number, index word
0 Parameter number does not exist Check data block number
1 Parameter value cannot be modified -
2 Minimum/maximum not reached or
exceeded
-
3 Subindex does not exist Check data block offset
4 Access to single value with array identifier Set data block offset = 0
5 Access to word with double word request or
vice versa
Use correct data type
(e.g. INT for word, DINT for double word)
6 Setting not allowed (resetting only) -
7 Descriptive element cannot be modified -
11 No status as master control -
12 Key word missing -
17
Request cannot be processed due to
operating state
-
101 Parameter number currently deactivated -
102 Channel not wide enough -
104 Illegal parameter value -
106 Request not implemented -
200/
201
Modified minimum/maximum not
reached/exceeded
Minimum/maximum can be further limited in
operation
No. 240-249: Parameter access is incorrectly formatted. Error detected on the PROFIBUS-DP
communication board.
Additional info in r2054.05, r2054.06: Parameter number or S7 data block number, subindex or S7
data block offset.
240 Error in variable address (no additional info) Legal: "Data block" area
241 Data block number illegally formatted Legal: 1...31999
242 Data block offset illegally formatted Legal: 0...116
243 Illegal "type"
Legal: CHAR. BYTE, INT, WORD, DINT,
DWORD, REAL
244 Illegal "Number of elements" on accessing
parameter value
Legal: Effectively 2 or 4 bytes
248 Illegal text/description modification -
249 Inconsistency in write request: "Type" and
"Number of elements" does not match "Data
type" and "Data length"
(error in communication partner)
No. 250: Parameter access has been converted to a PKW request. Response from converter is
errored. Error detected on the PROFIBUS-DP communication board. Additional info in r2054.05,
r2054.06: Parameter number, subindex.
250 PKW response does not match request (error in converter)
No. 251: Error detected on the PROFIBUS-DP communication board; no additional info
251 Response too long for response telegram (error in communication partner)