EasyManua.ls Logo

Siemens Micromaster Profibus - Parameter Index (IND) Structure; IND Structure for Cyclical and Acyclical Communication

Siemens Micromaster Profibus
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
&RPPXQLFDWLRQZLWK0,&520$67(5YLD352),%86'3 (GLWLRQ$
PROFIBUS Optional Board Operating instructions
28 6SE6400-5AK00-0BP0
3DUDPHWHULQGH[,1'
QG
ZRUG
,PSRUWDQW127(
$VVLJQPHQWVRILQGH[,1'GLIIHULQWKH332VDQGRQWKHDF\FOLFDOFKDQQHO
GDWDEORFN
6WUXFWXUHRI,1'IRUF\FOLFDOFRPPXQLFDWLRQYLD332V
PKE IND PWE1 PWE2
HIGH LOW
Array subindex MICROMASTER4-specific
15 8 7 0
Subindex 0- 255 Bit 7=PARA PAGE SEL
The array subindex (referred to simply as "subindex" in the PROFIDrive Profile) is
an 8-bit value which is transferred in the high-order byte (bits 8 to 15) of the
parameter index (IND) when data are transferred cyclically via PPOs. The low-
order byte (bits 0 to 7) is not defined in PROFIDrive Profile version 2.0. The low-
order byte of the parameter index is used on MICROMASTER4 to be able to
address additional parameters with a number of >1999.
6WUXFWXUHRI,1'IRUDF\FOLFDOFRPPXQLFDWLRQ
PKE IND PWE1 PWE2
HIGH LOW
MICROMASTER4-specific Array subindex
15 8 7 0
Bit 15 = PARA PAGE SEL Subindex 0- 255
The array subindex is an 8-bit value which is always transferred in the low-order
byte (bits 0 to 7) of the parameter index (IND) in acyclical data exchange mode.
The Parameter Page Selection task for additional parameters is performed in this
case by the high-order byte (bits 8 to 15) of the parameter index. This structure
conforms to the USS specification.

Table of Contents

Related product manuals