EasyManua.ls Logo

Siemens Micromaster Profibus - EMC Information; 8 Appendix; Technical Data

Siemens Micromaster Profibus
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
(GLWLRQ$ $SSHQGL[
PROFIBUS Optional Board Operating instructions
6SE6400-5AK00-0BP0
59
 $SSHQGL[
 7HFKQLFDOGDWD
Table 8-1 Technical data
Order number 6SE6400-1PB00-0AA0
Size
(height x width x depth) 161 mm x 73 mm x 43.5 mm
Pollution severity Pollution severity 2 according to IEC 664-1 (DIN VDE
0110/T1),
No moisture condensation permitted in operation
Mechanical strength
In stationary state
- Deflection
- Acceleration
During transportation
- Deflection
- Acceleration
Acc. to DIN IEC 68-2-6 (with correctly installed board)
0.15 mm in 10 Hz to 58 Hz frequency range
19.6 m/s
2
in > 58 Hz to 500 Hz frequency range
3.5 mm in 5 Hz to 9 Hz frequency range
9.8 m/s
2
in > 9 Hz to 500 Hz frequency range
Climate class Class 3K3 to DIN IEC 721-3-3 (in operation)
Cooling method Natural air cooling
Permissible ambient or
coolant temperature
- In operation
- In storage
- In transit
-10° C to +50° C (14° F to 122° F)
-25° C to +70° C (-13° F to 158° F)
-25° C to +70° C (-13° F to 158° F)
Permissible humidity rating Relative air humidity
<= 95 % in transit and storage
<= 85 % in operation (condensation not permissible)
Supply voltage 6.5 V ± 5 %, max. 300 mA, internal from basic converter
or 24V ± 10 %, max. 350 mA, from external source
Output voltage 5 V ± 10 %, max. 100 mA,
electrically isolated supply
- for the bus termination of the serial interface or
- for the supply of an OLP (Optical Link Plug)
Data transmission rate Max. 12 Mbaud
 (0&LQIRUPDWLRQ
The board complies with the following standards governing radio emissions and
interference immunity:
½ Radio emissions in accordance with EN55011 1991 Class A
½ Interference immunity in accordance with IEC 801-3 and EN61000-4-3