PROFIBUS Optional Board Operating instructions
24 6SE6400-5AK00-0BP0
Status word (bits 0-10 as per PROFIDrive Profile, bits 11-15 specific to
MICROMASTER4)
Table 3-2 Status word bit assignments
%LW 9DOXH 0HDQLQJ 5HPDUNV
0 1 Ready for ON Power supply switched on, electronics initialized, pulses
disabled
0 Not ready for ON
1 1 Ready to run (see control word bit 0)
Converter is switched on (ON command is applied), no fault
is active, converter can start when "Enable operation"
command is issued.
0 Not ready to run Causes: No ON command, fault, OFF2 or OFF3 command,
starting lockout
2 1 Operation enabled See control word, bit 3
0 Operation disabled
3 1 Fault is active
Fault, see fault parameter r0947 etc.
Drive is faulty and thus inoperative, switches to starting
lockout state after successful correction and
acknowledgement of fault.
0-
41 -
0 OFF2 command applied See control word, bit 1
51 -
0 OFF3 command applied See control word, bit 2
6 1 Starting lockout Drive can be restarted only by OFF1 followed by ON
0 No starting lockout
7 1 Alarm is active Alarm, see alarm parameter r2110.
Drive still in operation.
0-
8 1 No setpoint/act.val.
deviation
Setpoint/actual value deviation within tolerance range
0 Setpoint/act.val. deviation
9 1 Master control requested The master is being requested to accept status as master
control.
0 Local operation The master is not currently the master control.
10 1 f reached
Converter output frequency is higher or equal to the
maximum frequency
0 f not reached
11 1
0 Alarm: Motor at current limit
12 1 Signal can be used to control a holding brake.
0 Motor holding brake
13 1 Motor data indicate overload condition
0 Motor overload
14 1 CW rotation
0 CCW rotation
15 1 e.g. current or temperature
0 Converter overload